Abstract: In this study, we designed a multifunctional heat pump system using just one scroll compressor and which can be run in four different modes, namely air to air, air to water, water to water and water to air, in order to make an experimental energetic and exergetic performance comparison. Experimental system consists of two condensers and two evaporators and uses R22 as working fluid. One of the evaporators and condensers uses water and the others use air as heat source/sink. Heating capacities of four heat pump types are equal to each other. It ...